PipeAlarm LX
Flexible Monitoring Solution for District Heating Pipe Networks
The PipeAlarm LX from LANCIER Monitoring is the compact, battery-powered monitoring solution for district heating pipelines equipped with a pair of monitoring conductors in the insulating layer. With additional contact inputs and wireless communication, the PipeAlarm LX operates completely independently of a local power supply or network connection. Easy to install and operate, the system provides reliable monitoring even at remote measuring points without the need for complex infrastructure.
In the event of a fault, alarms are transmitted reliably via common wireless communication standards such as LTE, LoRaWAN, 450 MHz or NB-IoT. This ensures that you remain fully informed even at remote measuring points – without the need for complex infrastructure. The modular system monitors up to four channels (= 8 measured values) simultaneously in the supply and return lines of the pipeline.
The insulation resistance and loop resistance of a pair of conductors in the insulating layer of the pipe are measured in accordance with EN 14419. The system is suitable for Nordic and hierarchical systems as well as NiCr systems. Two additional potential-free contact inputs allow external signals, e.g. from float switches or door contacts, to be integrated. An integrated temperature sensor also monitors the ambient temperature.
In the event of pipe leaks, interruptions in the measuring loop, faulty connections or changes in the status of the contact inputs, the PipeAlarm LX triggers an alarm. This enables costly damage to be detected at an early stage and helps prevent system failures.
Communication with the UMS2 platform is reliably provided via common wireless communication standards such as LTE, LoRaWAN, 450 MHz or NB-IoT. Reading measured values, setting limit values or adjusting configurations can all be carried out conveniently via wireless communication using LANCIER Monitoring’s browser-based UMS2 platform or locally via the USB-C interface.
The UMS2 platform provides reliable, flexible and user-friendly monitoring with precise alarm notification, ensuring maximum operational reliability with minimum effort.
Intelligent Data Acquisition and Communication
- Automatic daily measurements (shorter measurement intervals can be configured as required)
- Input contacts are polled every 10 seconds
- Weekly status report including device status
- Secure storage of the latest 90 measured values per channel in the internal EEPROM memory
Ordering Data
| PipeAlarm LX Flexible Monitoring Solution for District Heating Pipe Networks Accessories | Order-no. 077280.00X |
| Antenna extension LTE/GSM antenna extension cable, 5 m long | Order-no. 075560.000 |
| External plug-in power supply, 5 V Lithium-Battery 3.6 V with bracket and connection cable | Order-no. 077197.000 Order-no. 075969.000 |
Technical Data
| PipeAlarm LX short | PipeAlarm LX | |
| Supply voltage | Replaceable lithium battery, 3.6 V or power supply 3.3 – 5 V | |
| Battery lifetime | > 5 years (1 measurement/day, 1 status report/week) | |
| Measurement channels | 2 (e. g. for flow and return line of a district heat pipe) | |
| Measurement range insulation | 0 .. 5.0 MΩ fault: 3 % of measured value ±10 kΩ absolute | 0 .. 50 MΩ fault: 3 % of measured value ±10 kΩ absolute |
| Measurement range loop | 0 .. 5.0 kΩ fault: 3 % of measured value ±0.02 kΩ absolute | 0 .. 9.99 kΩ fault: 3 % of measured value ±0.02 kΩ absolute |
| Measuring distance | Nordic / Hierarchical ≤ 3.000 m NiCr ≤ 750 m | Nordic / Hierarchical ≤ 3.000 m NiCr ≤ 1.500m |
| Length calculation | no | yes, for NiCr |
| Measuring voltage | 24 V DC | |
| Contacts | 2 contact inputs, line length < 30 m (e.g. float switches), continuously monitored | |
| Measuring range temperature | -20 °C .. +140 °C, Resolution 1 %, Fault 3 % +1 Digit | |
| Display | Color display | |
| On-site operation | Display, push button for real-time measurement and sending a test message, 1 USB-C interface for device configuration | |
| Interfaces | USB, temporary, for configuration | |
| Operating temperature | -20 °C .. +50 °C | |
| Admissible humidity | 0 .. 100 % | |
| Degree of protection by enclosure | IP 66 | |
| Field of application | Indoor and sheltered installation according to DIN VDE 0100 part 737. residential and business area as well as small enterprises | |
| Dimensions (w x d x h) | 271 x 170 x 90 mm | |