Skip to main content

LAB-Supply 2022
Jun-Air und LANCIER Monitoring sind dabei, bei der LAB-Supply:
19.10.2022 LAB-SUPPLY Sindelfingen, 09.11.2022 LAB-SUPPLY Münster

 

mehr lesen

RTU 101-IMS

for monitoring insulation- and loop resistance in copper cables

The monitoring station RTU 101-IMS is used to detect the penetration of moisture in copper cables, their squeezing or damage.

The readings of the 10 measurement channels, regarding insulation and loop resistance, are evaluated by the RTU 101-IMS according to individual user programmed parameters.

Threshold exceedings cause automatic reports like warnings, alarms etc. to assigned receiving stations.

The UMS server permanently polls the actual measurement and system data via intranet (Ethernet, TCP/IP). It evaluates the sensing points states and stores all data in the database of the UMS server.

All connections and control units are stored in awall mount housing. The connections are fixed by screws and clamps ensuring an easy and cost effective mounting without the need ofexpensive special cables.

Technical Data

Supply voltage21 .. 72 V DC
Power consumptiontyp. 10 VA DC
No. of measurement channels10 for loop- and insulation resistance each
Measurement rangeInsulation measurement
0,01 ... 500 MΩ
Loop resistance measurement
50 ... 20.000 Ω
Resolutionup to 0,01 MΩup to 1 Ω
Max. measurement error10% of measured value ± 50 kΩ± 3% of measured value
Test voltage30 V or 90 V DC
Local alarm signalisation13 dry contacts
Operating temperature0 .. +40 °C
Storage temperature-5 .. +60 °C
EMC61000-6-1/2 and 61000-6-3/4
Data back upBattery buffer (2 years)
Dimensions (H x W x D)237 x 355 x 150 mm
Weightapprox. 3,2 kg

We are member of the following organisations: