Monitoring Station RTU

for universal monitoring tasks

The monitoring station RTU is an universal platform for the permanent surveillance of copper or fiber network and related equipment. Its modular set-up by IEC-boards allows for the solving of very different measurement tasks. It measures the connected sensors, contacts and modules continuously and evaluates the results according to programmed thresholds.

The central UMS server permanently polls the actual time coded measurement, alarm and system data via intranet (Ethernet,TCP/IP).

The trap function of the RTU can forward status signals to superior systems. The use of the SNMP protocol allows for direct integration into TMN systems.

All connections and control units are stored in a19’’ housing.

Ordering Data

Monitoring Station RTU
   36 ..75 V DC (DC/DC power supply unit)
   100 .. 250 V AC/45 .. 65 Hz (AC/DC power supply unit)


Order-no067400.000
Order-no. 067400.008

Spare parts/Accessories
   CPU card RTU
Connection cable
   RS232,
 1.8 m, 9-pin SUB-D male/female
   CAN, 3 m, 9-pin, SUB-D female
   Communication module I-COM for RTU (analogue)
   with internal modem
   Interface card I-OTDR
   Interface caed I-OSW

Order-no. 072413.000

Order-no. 073134.000
Order-no. 073135.000
Order-no. 072445.001

Order-no. 071496.000
Order-no. 071517.000
Further odering data
   OTDR module,
 2 HU, 1625 nm, 40 dB, complete 
   (interface card and cable included)
   Optical switch module, Z HE, 1xX, complete

Order-no.070677.0YY

Order-no. 073XXX.0YY
X, Y and Z depending an configuration 

Technical Data

DC/DC-power supply unit (specifications for 60V)
Input voltage
Current consumption


Power consumption

36 .. 75 V DC
approx. 150 mA without measurement cards, additionally approx. 40 mA per installed card
<10 VA without measurement cards, additionally approx. 2.5 VA per installed card
AC/DC-power supply unit (specifications for 230V)
Input voltage
Current consumption


Power consumption


Output voltage
   galvanically isolated
   and short-circuit proof
   (maximum current)

100 .. 250 V AC/45 .. 65 Hz
approx. 70 mA without measurement cards, additionally approx. 10 mA per installed card
<18 VA without measurement cards, additionally approx. 2.5 VA per installed card
U1 = 5 V DC (8 A)
U2 = 12 V DC (2 A)
U3 = 12 V DC (2 A)
U4 = 60 V DC (0,1 A)
RTU
LEDs

U1, U2, U3, U4 (function check)
Operating temperature range0 .. +55 °C
Storing temperature range-20 .. +60 °C
Admissible humidity0 .. 95 % rel. humidity, non-condensing
Dimensions (H x W x D)min. 266 x 483 x 310 mm, dimension for mounting into 19’’-Rack
Weight without cards< 10 kg
Slots12 for measurement cards in IEC format
Dimensions measurem. cardsFront plate 4 TE x 3 HE, PCB approx. 100 x 160 mm
EMC61000-6-1/2 and 61000-6-3/4
Communication modules dimensions
I-COM for RTU (analogue)
Interface card I-OTDR
Interface card I-OSW

Front plate 8 TE x 3 HE, PCB 100 x 160 mm
Front plate 4 TE x 3 HE. PCB 100 x 160 mm
Front plate 8 TE x 3 HE, PCB 100 x 160 mm
CPU card
Embedded Controller
Operating system
Storing capacity



Memory buffer
RTC

Interfaces
   Ethernet
   RS232

   CAN

LEDs
Operating elements
Dimensions

PowerPC MPC565 32-Bit 40 MHz
RTEMS
SRAM      2 MB (8 MB Option)
Flash      2 MB (8 MB Option)
RAMDisk 2 MB (12 MB Option)

approx. 1 year by battery
12/24 hrs., programmable alarms and/or periodical interrupts

10 Mbit BaseT, connector RJ45
9600 Baud 8N1, connector female 9-pin SUB-D
9600 Baud 8N1, connector female 9-pin SUB-D
LINK, TRAFFIC
Reset button
Front plate 4 TE x 3 HE, PCB approx. 100 x 160 mm
Software
Accessible hardware


Storing capacity

64 Devices, 10 measurement buses, parallel measurement of all measurement cards
max. 750 sensors, max. 50 OTDR-traces (at 2MB RAMDisk)