The monitoring station RTU is an universal platform for the permanent surveillance of copper or fiber network and related equipment. Its modular set-up by IEC-boards allows for the solving of very different measurement tasks. It measures the connected sensors, contacts and modules continuously and evaluates the results according to programmed thresholds.
The central UMS server permanently polls the actual time coded measurement, alarm and system data via intranet (Ethernet,TCP/IP).
The trap function of the RTU can forward status signals to superior systems. The use of the SNMP protocol allows for direct integration into TMN systems.
All connections and control units are stored in a19’’ housing.
Monitoring Station RTU 36 ..75 V DC (DC/DC power supply unit) 100 .. 250 V AC/45 .. 65 Hz (AC/DC power supply unit) |
|
Spare parts/Accessories CPU card RTU Connection cable RS232, 1.8 m, 9-pin SUB-D male/female CAN, 3 m, 9-pin, SUB-D female Communication module I-COM for RTU (analogue) with internal modem Interface card I-OTDR Interface caed I-OSW | Order-no. 072413.000 Order-no. 073134.000 Order-no. 073135.000 Order-no. 072445.001 Order-no. 071496.000 Order-no. 071517.000 |
Further odering data OTDR module, 2 HU, 1625 nm, 40 dB, complete (interface card and cable included) Optical switch module, Z HE, 1xX, complete | Order-no.070677.0YY Order-no. 073XXX.0YY |
X, Y and Z depending an configuration |
DC/DC-power supply unit (specifications for 60V) Input voltage Current consumption Power consumption | 36 .. 75 V DC approx. 150 mA without measurement cards, additionally approx. 40 mA per installed card <10 VA without measurement cards, additionally approx. 2.5 VA per installed card |
AC/DC-power supply unit (specifications for 230V) Input voltage Current consumption Power consumption Output voltage galvanically isolated and short-circuit proof (maximum current) | 100 .. 250 V AC/45 .. 65 Hz approx. 70 mA without measurement cards, additionally approx. 10 mA per installed card <18 VA without measurement cards, additionally approx. 2.5 VA per installed card U1 = 5 V DC (8 A) U2 = 12 V DC (2 A) U3 = 12 V DC (2 A) U4 = 60 V DC (0,1 A) |
RTU LEDs | U1, U2, U3, U4 (function check) |
Operating temperature range | 0 .. +55 °C |
Storing temperature range | -20 .. +60 °C |
Admissible humidity | 0 .. 95 % rel. humidity, non-condensing |
Dimensions (H x W x D) | min. 266 x 483 x 310 mm, dimension for mounting into 19’’-Rack |
Weight without cards | < 10 kg |
Slots | 12 for measurement cards in IEC format |
Dimensions measurem. cards | Front plate 4 TE x 3 HE, PCB approx. 100 x 160 mm |
EMC | 61000-6-1/2 and 61000-6-3/4 |
Communication modules dimensions I-COM for RTU (analogue) Interface card I-OTDR Interface card I-OSW | Front plate 8 TE x 3 HE, PCB 100 x 160 mm Front plate 4 TE x 3 HE. PCB 100 x 160 mm Front plate 8 TE x 3 HE, PCB 100 x 160 mm |
CPU card Embedded Controller Operating system Storing capacity Memory buffer RTC Interfaces Ethernet RS232 CAN LEDs Operating elements Dimensions | PowerPC MPC565 32-Bit 40 MHz RTEMS SRAM 2 MB (8 MB Option) Flash 2 MB (8 MB Option) RAMDisk 2 MB (12 MB Option) approx. 1 year by battery 12/24 hrs., programmable alarms and/or periodical interrupts 10 Mbit BaseT, connector RJ45 9600 Baud 8N1, connector female 9-pin SUB-D 9600 Baud 8N1, connector female 9-pin SUB-D LINK, TRAFFIC Reset button Front plate 4 TE x 3 HE, PCB approx. 100 x 160 mm |
Software Accessible hardware Storing capacity | 64 Devices, 10 measurement buses, parallel measurement of all measurement cards max. 750 sensors, max. 50 OTDR-traces (at 2MB RAMDisk) |