IsoTxA-Mk2
Insulation and Loop Resistance
The IsoTxA-Mk2 is a stand-alone measurement and monitoring device for insulation and loop resistance. A dedicated copper pair is used as a measurement loop in the monitored cable. This loop is being measured continuously by the IsoTxA-Mk2. The thresholds for the insulation and loop resistance values are easily programmable with the built-in keys. The integrated display shows the measurement values andsettings.
Dry output relay contacts are built-in for remote alarming. Additionally the IsoTxA-Mk2 can be equipped with plug-in interface modules for LANCIER Tx-Bus, CAN-Bus or telecontrol systems via Modbus by RS485 interface.
Ordering Data
IsoTxA-Mk2 Module with display and keys. Signal output via dry contacts. For insertion into 19"- drawer (1 HU). | Order-no. 071676.000 | |
Lancier Tx-Bus Interface Internal plug-in module for connection to montioring systems DW 1005E or DW 101E | Order-no. 071700.000 | |
CAN - Interface Internal plug-in module for connection to RTU or ethernet via CAN-ethernet adaptor | Order-no. 072050.000 | |
Modbus-Interface Internal plug-in module | Order-no. 073601.000 | |
Other interfaces upon request | ||
CAN - Ethernet adaptor External module for connection of several transducers to TMN / Lancier UMS via SNMP | Order-no. 072240.000 | |
Drawer 19" 1HU for max. three Mk2 sensors | Order-no. 071863.000 |
Technical Data
Measurement range insulation | 0 - 200 MΩ |
Resolution | 0,1 MΩ bei 0 - 100 MΩ 1,0 MΩ bei 100 - 200 MΩ |
Measurement range loop | 0 -10 kΩ |
Resolution | 10 Ω |
Supply voltage | 36 - 72 VDC |
Power consumption | 50 mA typ. |
Display | 3-digit, LCD, insulation and loop resistance switchable |
Signal LEDs | 2 x red, Alarm insulation and loop 2 x yellow, Acknowledged alarm insulation and loop 2 x green, Display insulation and loop resistance 1 x red, Remote operation |
Local User Interface | Set threshold insulation resistance Acknowledge insulation alarm Set threshold loop resistance Acknowledge loop alarm |
Signal outputs | 2 dry change-over contacts for: insulation resistance, loop resistance |
Max. switchable voltage / current | 100 V DC / 0,1 A DC |
Dimensions sensor | 40,3 x 129 x 167 mm |
Dimensions drawer | 42 x 484 x 278-353 mm (1HU/19") |