Skip to main content

LAB-Supply 2022
Jun-Air und LANCIER Monitoring sind dabei, bei der LAB-Supply:
19.10.2022 LAB-SUPPLY Sindelfingen, 09.11.2022 LAB-SUPPLY Münster

 

mehr lesen

IsoTxA-Mk2

Insulation and Loop Resistance

The IsoTxA-Mk2 is a stand-alone measurement and monitoring device for insulation and loop resistance. A dedicated copper pair is used as a measurement loop in the monitored cable. This loop is being measured continuously by the IsoTxA-Mk2. The thresholds for the insulation and loop resistance values are easily programmable with the built-in keys. The integrated display shows the measurement values andsettings.

Dry output relay contacts are built-in for remote alarming. Additionally the IsoTxA-Mk2 can be equipped with plug-in interface modules for LANCIER Tx-Bus, CAN-Bus or telecontrol systems via Modbus by RS485 interface.

Ordering Data

IsoTxA-Mk2
Module with display and keys. Signal output via dry contacts.
For insertion into 19"- drawer (1 HU).


Order-no. 071676.000
Lancier Tx-Bus Interface Internal plug-in module
for connection to montioring systems DW 1005E or DW 101E

Order-no. 071700.000
CAN - Interface Internal plug-in module
for connection to RTU or ethernet via CAN-ethernet adaptor

Order-no. 072050.000

Modbus-Interface Internal plug-in module
for connection to a telecontrol system via Modbus by RS485 interface



Order-no. 073601.000
Other interfaces upon request 
CAN - Ethernet adaptor External module 
for connection of several transducers to TMN / Lancier UMS via SNMP


Order-no. 072240.000
Drawer 19" 1HU for max. three Mk2 sensorsOrder-no. 071863.000

Technical Data

Measurement range insulation0 - 200 MΩ
Resolution0,1 MΩ bei 0 - 100 MΩ
1,0 MΩ bei 100 - 200 MΩ
Measurement range loop0 -10 kΩ
Resolution10 Ω
Supply voltage36 - 72 VDC
Power consumption50 mA typ.
Display3-digit, LCD, insulation and loop resistance switchable
Signal LEDs2 x red, Alarm insulation and loop
2 x yellow, Acknowledged alarm insulation and loop
2 x green, Display insulation and loop resistance
1 x red, Remote operation
Local User InterfaceSet threshold insulation resistance
Acknowledge insulation alarm
Set threshold loop resistance
Acknowledge loop alarm
Signal outputs2 dry change-over contacts for: insulation resistance, loop resistance
Max. switchable voltage / current100 V DC / 0,1 A DC
Dimensions sensor40,3 x 129 x 167 mm
Dimensions drawer42 x 484 x 278-353 mm (1HU/19")

We are member of the following organisations: