Monitoring Station RTU-Cu8

Insulation and loop resistance monitoring station with time domain reflectometer for fault location

The RTU-Cu8 monitoring station surveilles the insulation and loop resistance of copper cables in the LANCIER Monitoring UMS system.

The integrated multiplexer module allows for the monitoring of 8 measuring pairs with only one measuring device.

If the RTU-Cu8 detects faults on one of the measuring pairs, the optional TDR module is automatically switched on for fault location. In this way, the location of the fault is determined within a very short time and troubleshooting can be initiated immediately.

A free pair in the cable sections that is to be monitored serves as a measuring loop, which is continuously measured by the RTU-Cu8. The alarm threshold for insulation and loop resistance are freely programmable via an integrated keypad and the integrated display. All settings are saved in an internal EEPROM memory to prevent losses.

For remote alarming, the RTU-Cu8 has built-in dry contact outputs. In addition, it can be connected to a remote control system via Modbus.

The RTU-Cu8 quickly and precisely detects and locates cable breaks caused by construction activities, cable theft or sabotage, for example.

TDR is equipped with Color Touchscreen!

Ordering Data

Monitoring station RTU-Cu8
Insulation and loop resistance measuring system
equipped with control panel and signal output via dry contacts

Order-no. 076860.000

Monitoring station RTU-Cu8 plus
additionally equipped with time-domain reflectometer measuring module
for fault location with color touch screen  

Order-no. 076861.000

TDR-Module
for retrofitting with time domain reflectometer measuring module
for fault location with color touch screen
Order-no. 074714.001

Technical Data

RTU-Cu8 
Number of Measurement channels8
Operating temperature-20 .. +40 °C
Admissible ambient humidity0 .. 95 %, humidity, non-condensing
Dimensions (W x H x D)546 x 416 x 186 mm
  
Resistance measurement 
Insulation resistance
Measurement range  /  Resolution   
0 .. 1 M / 0,001 MΩ, fault ± 5 % of measurement ±0,01 MΩ
1 .. 200 MΩ / 0,01 MΩ, fault ± 5 % of measurement ±0,01 MΩ
Loop resistance
Measurement range  /  Resolution
0 .. 10 kΩ / 0,001 kΩ, fault ± 5 % of measurement ±0,05 kΩ
Measuring voltage90 V DC
Signal LEDs 2 x green / red: Alarm / Acknowledged alarm / Display operation insulation resp. loop
1 x blue: display operation
Signal outputs2 dry change-over contacts for: insulation and loop resistance
Max. switchable voltage / current     100 V DC   /   0.1 A DC
Fault location via TDR (optional) 
Measurement range62.5 .. 64,000 m
Location fault

0.01 % .. 0.2 % of the measured value (12.5 cm to 8.0 m, depending on the subsections)

Impedance30 .. 500 Ω, adjustable
Impulse width10 ns .. 50 μs
V/250.0 .. 150.0 m/μs
Impulse amplitude10 V with matched load
Input sensitivity1 mV
Dynamic range80 dB
Signal outputdry change-over contact for: impedance
Max. switchable voltage / current     100 V DC   /   0.1 A DC